If there hree QC30TR I QC30TR /O station, station 1, I input station, station 2 Station No. 3 to O output, IO input and output station, all occupy a site, then No. 1 station is occupied by the output register RY, the No. 2 station is occupied by the input registers RX?
Re:   Time: 9/12/2017 10:27:00 PM
In fact, there is no occupation relationship, I/O is mainly based on station number to be assigned, the above situation 1 station to use RXF~RX0, station 2 to use RY2F~RY20, station 3 to use RX47~RX40 and RY4F~RY48.
Re:Re:   Time: 9/13/2017 12:51:00 AM
I see. Thank you!
Re:Re:Re:   Time: 9/13/2017 5:39:00 AM
You are welcome. I am glad to be able to handle your queries. You are welcome to leave a message again or call our technical support hotline 400--.